The North American Electric Reliability Corporation's Board of Trustees voted on October 26 to adopt the organization's first foundational reliability standards specifically covering large computational loads — a category that includes AI data centers, cloud facilities and cryptocurrency mining operations. The standards, developed under Project 2026-02, passed their final stakeholder ballot on October 14 and will now be filed with the Federal Energy Regulatory Commission for regulatory approval in the United States.
The rules apply to any computational load site drawing 50 megawatts or more of power through equipment connected at 100 kilovolts or above. Three new standards form the core of the package. The first covers interconnection studies and modeling data, requiring facilities to share protection settings and run commissioning tests that simulate real voltage swings. The second covers operational data and communications between the site and grid operators. The third covers load protection coordination and disturbance monitoring, including fault recorders capable of capturing grid events. Existing sites are expected to have 36 months to install the required fault recorders.
The standards grew out of a series of incidents in which large data centers abruptly dropped load during minor grid disturbances, causing ripple effects across regional transmission networks. The most significant was a July 22 event in northern Virginia, where roughly 3,800 megawatts of data center load tripped offline — the largest such event in PJM Interconnection's history. FERC directed NERC to file the new standards by December 31, 2026. ERCOT, which manages the Texas grid, had already enacted its own ride-through requirements effective August 1.
Organizations operating data centers at the 50 MW and 100 kV threshold — or planning facilities that will reach it — may want to review whether their protection settings, metering and interconnection agreements align with what the new standards will require. The FERC filing and final approval process is still ahead, and NERC has signaled that a second phase of standards addressing minimum voltage and frequency ride-through performance requirements will follow.